The 5123-C2 from Taco is a 3/4” Union Sweat Mixing Valve (Lead-Free), ASSE 1070, 85F-120F. It's designed for use at the water heater to distribute controlled water temperatures to the domestic hot water system and is suitable for use in Potable Water.
Taco's new 5123-C2 Low Lead Mixing Valve makes it ideal for use in the distribution of water through a domestic hot water system. The valve's unique design and advanced thermostatic element doesn't require routine maintenance and ensures a stable mixed water temperature throughout the valves adjustable range. The Second-generation material was tested and calibrated under closely controlled conditions ensuring durability and functionality.
Materials
Features:
Technical Specifications:
Product Specs | |
Accuracy of Outlet Temperature: | ± 3°F |
Approvals: | ASSE 1017 / 1070, CSA125.3, cUPC. |
Cold Supply Temperature: | 39-80°F (5-27°C) |
Connections: | 3/4" Union Sweat |
Factory Set to: | 115-120°F (41-45°C) |
Features: | Lead Free |
Heat Capacity: | 1.8 Cv |
Hot Supply Temperature: | 120-180°F (49-82°C) |
Maximum Flow: | 14 GPM (54 L/Min) |
Maximum Inlet Pressure: | 200 psi (13.8 Bar) |
Maximum Variation in Supply Pressure: | 20% |
Minimum Flow: | 1 GPM (3.8 L/Min) |
Minimum Temperature Differential Between Hot Supply and Mixed: | 27°F (15°C) |
Outlet Temperature Range: | 85-120°F (29-49°C) |